Expansion i/o specifications, Digital i/o modules – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual
Page 176

134
Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
Appendix A Specifications
Expansion I/O
Specifications
Digital I/O Modules
Output Group to Backplane Isolation
Verified by one of the following dielectric tests: 1836V AC for 1 second or 2596V DC for 1 second
265V AC Working Voltage (IEC Class 2 reinforced insulation).
Output Group to Output Group
Isolation
Verified by one of the following dielectric tests: 1836V AC for 1 second or 2596V DC for 1 second
265V AC Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2 reinforced insulation)
Working Voltage for 1766-L16BXB/A
Description
Recommendation
Input Group to Backplane Isolation and
Input Group to Input Group Isolation
Verified by one of the following dielectric tests: 1100V AC for 1 second or 1697V DC for 1 second
75V DC Working Voltage (IEC Class 2 reinforced insulation)
FET Output Group to Backplane
Isolation
Verified by one of the following dielectric tests: 1100V AC for 1 second or 1697V DC for 1 second
75V DC Working Voltage (IEC Class 2 reinforced insulation)
Relay Output Group to Backplane
Isolation
Verified by one of the following dielectric tests: 1836V AC for 1 second or 2596V DC for 1 second
265V AC Working Voltage (IEC Class 2 reinforced insulation)
Relay Output Group to Relay Output
Group and FET Output Group Isolation
Verified by one of the following dielectric tests: 1836V AC for 1 second or 2596V DC for 1 second
265V AC Working Voltage (basic insulation), 150V Working Voltage
(IEC Class 2 reinforced insulation)
Working Voltage for 1766-L32BWA/A
General Specifications
Specification
Value
Dimensions
90 mm (height) x 87 mm (depth) x 40.4 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in. (depth) x 1.59 in. (width)
height including mounting tabs is 4.33 in.
Temperature, storage
-40 °C…85 °C (-40…185 °F)
Temperature, operating
-20…65 °C (-4…149 °F)
(1)
Operating humidity
5…95% non-condensing
Operating altitude
2000 m (6561 ft)
Vibration
Operating: 10...500 Hz, 5 g, 0.030 in. max. peak-to-peak, 2 hours per axis
Relay Operation: 1.5 g
Shock
Operating: 30G panel mounted, 3 pulses per axis
Relay Operation: 7 g
Non-Operating: 50 g panel mounted, 3 pulses per axis
(40G DIN Rail mounted)
Agency Certification
C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
C-Tick marked for all applicable acts