Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual
Page 180
138
Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
Appendix A Specifications
Vendor I.D. code
1
Product type code
7
Product code
119
101
103
100
102
Output Specifications
Specification
1762-OA8
1762-OB8
1762-OB16
1762-OB32T
1762-OV32T
Output Specifications
Specification
1762-OW8
1762-OW16
1762-OX6I
1762-IQ8OW6
Shipping weight, approx.
(with carton)
228 g (0.50 lbs.)
285 g (0.63 lbs.)
220 g (0.485 lbs)
280 g (0.62 lbs.)
Voltage category
AC/DC normally open
relay
AC/DC normally open
relay
AC/DC Type C Relay
AC/DC normally open
relay
Operating voltage range
5…265V AC
5…125V DC
5…265V AC
5…125V DC
5…265V AC
5…125V DC
5…265V AC
5…125V DC
Number of outputs
8
16
6
6
Bus current draw, max.
80 mA at 5V DC
(0.40W)
90 mA at 24V DC
(2.16W)
140 mA at 5V DC
(0.70W)
180 mA at 24V DC
(4.32W)
(1)
110 mA at 5V DC
(0.55W)
110 mA at 24V DC
(2.64W)
110 mA at 5V DC
80 mA at 24V DC
Heat dissipation, max.
2.9 W
6.1 W
2.8 W
5.0 W at 30V DC
4.4 W at 26.4V DC
(The Watts per point,
plus the minimum W,
with all points
energized.)
Signal delay, max. –
resistive load
On Delay: 10 ms
Off Delay: 10 ms
On Delay: 10 ms
Off Delay: 10 ms
On Delay: 10 ms (max)
6 ms (typical)
Off Delay: 20 ms (max)
12 ms (typical)
On-delay: 10 ms (max)
Off-delay: 10 ms (max)
Off-state leakage, max.
0 mA
0 mA
0 mA
0 mA
On-state current, min.
10 mA
10 mA
100 mA
10 mA
On-state voltage drop,
max.
Not Applicable
Continuous current per
point, max.
2.5 A (Also see “Relay Contact Ratings” on page
139.)
7 A (Also see “Relay
Contact Ratings” on
page 139.)
2.5 A (Also see “Relay
Contact Ratings” on
page 139.)
Continuous current per
common, max.
8 A
8 A
7 A (Also see “Relay
Contact Ratings” on
page 133.)
8 A
Continuous current per
module, max.
16 A
16 A
30A (Also see
Load Ratings
1762-OX6I on page
140
.)
8A
Surge current, max.
See “Relay Contact Ratings” on page 139.
See “Relay Contact
Ratings” on page 139.
See “Relay Contact
Ratings” on page 139.
Isolated groups
Group 1: Outputs 0 to
3
Group 2: Outputs 4 to
7
Group 1: Outputs 0 to
7
Group 2: Outputs 8 to
15
All 6 Outputs
Individually Isolated.
Group 3:
Outputs 0 to 5
Output group to
backplane isolation
Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s.
265V AC working voltage (IEC Class 2 reinforced insulation)