MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F
For Small BCD type data, you can configure Class information in the
Configuration file. The lower 2 bits in each element of the Configuration files are
the configuration of Class information to the relevant objects. P0 bit in the first
element is for excluding Small BCD Data from Class 0 poll responses. Other bits
are reserved.
Related Configuration File Numbers:
• Small BCD Config File Number
DNP3 Binary Input Object
The supported object group and variations are listed in this section. The
MicroLogix 1400 responds with the default group and variation when the DNP3
Master requests to read the object with all variations.
Binary Input Static Objects:
• g1v0 - Binary Input - All Variations
Analog Output Configuration Data File
Bit Offset
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Element 0
F7
F6
F5
F4
F3
F2
F1
F0
r
r
r
r
r
r
r
r
Element 1
F7
F6
F5
F4
F3
F2
F1
F0
r
r
r
r
r
r
r
r
Element 2
F7
F6
F5
F4
F3
F2
F1
F0
r
r
r
r
r
r
r
r
Element 3
F7
F6
F5
F4
F3
F2
F1
F0
r
r
r
r
r
r
r
r
Element 4
F7
F6
F5
F4
F3
F2
F1
F0
r
r
r
r
r
r
r
r
Element 5
F7
F6
F5
F4
F3
F2
F1
F0
r
r
r
r
r
r
r
r
…
r: reserved
F7-F0: Object Flags, FLAG7/FLAG6/FLAG5/LOCAL_FORCED/REMOTE_FORCED/COMM_LOST/RESTART/ONLINE
Small BCD Configuration File Data
Bit Offset
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Element 0
r
r
r
r
r
r
r
r
PO
r
r
r
r
r
C1
C0
Element 1
r
r
r
r
r
r
r
r
r
r
r
r
r
r
C1
C0
Element 2
r
r
r
r
r
r
r
r
r
r
r
r
r
r
C1
C0
Element 3
r
r
r
r
r
r
r
r
r
r
r
r
r
r
C1
C0
Element 4
r
r
r
r
r
r
r
r
r
r
r
r
r
r
C1
C0
Element 5
r
r
r
r
r
r
r
r
r
r
r
r
r
r
C1
C0
…
C1
C0
r: reserved
C1/C0 : Class level, 0 to 3
For Small BCD, Element_0 for data index 0
P0: 0 for including Small BCD Data to Class 0 poll response