Dnp3 data files – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual
Page 276
![background image](/manuals/579250/276/background.png)
236
Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
Appendix F MicroLogix 1400 Distributed Network Protocol (DNP3)
DNP3 Data Files
Basically, the index number of DNP objects of each type is evaluated by the
firmware automatically per the number of elements. For example, if a Binary
Input object file was configured as an element, the highest index number of the
Binary Input object is 15. The index number can only be increased by 16. If a
Double-Bit Binary Input object file was configured as an element, the highest
index number of the Double-Bit Binary Input object is 7. The index number can
only be increased by 8.
As another example, if a 16-bit Analog Input object file was configured as an
element, the highest index number is 1. Except for Binary and Double-Bit Binary
type objects, the index number can be increased by 1.
Relationship between DNP3 object database and MicroLogix data files
DNP Objects
Micrologix Data Files
Object Name
Related
Groups
Maximum
Configurable
Index
File name for Data
File Type
File
Number
Maximum
Configurable
Elements
Binary Input Object
1, 2
4096
Binary Input Object File
Only B file
3, 9 to 255
256
Double Bit Binary Input
Object
3, 4
2048
Double Bit Binary Input Object File
Only B file
3, 9 to 255
256
Binary Output Object
10, 12
4096
Binary Input Object File
Only B file
3, 9 to 255
256
Counter Object
20, 22
256
16-bit Counter Object File
Only N file
7, 9 to 255
256
32 bit Counter Object File
Only L file
9 to 255
Frozen Counter Object
21, 23
reflection of
Counter Object
which was
configured
reflection of 16-bit Counter Object File
-
-
-
reflection of 32-bit Counter Object File
Analog Input Object
30, 32
256
16-bit Analog Input Object File
Only N file
7, 9 to 255
256
32-bit Analog Input Object File
Only L file
9 to 255
Short Floating Point Analog Input Object File Only F file
8, 9 to 255
Analog Output Object
40, 41
256
16-bit Analog Output Object File
Only N file
256
32-bit Analog Output Object File
Only L file
9 to 255
Short Floating Point Analog Output Object
File
Only F file
8, 9 to 255
BCD Object
101
256
Small BCD Object File
Only N file
7, 9 to 255
256
Data Set Object(In
Series B)
85, 87, 88
10
Data Set Prototypes Object File
Only N file
7, 9 to 255
10
86, 87, 88
Data Set Descriptors Object File