Master ip address0, Remote tcp port number, Remote udp port number for initial unsolicited – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual
Page 251: Remote udp port number, Master node1, master node2

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
211
MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F
Master Node1, Master Node2, Master Node3, Master Node4
This value is used for validation of the Master node address when the Enable
Master Address Validation is Enabled (Checked). This value is only valid when
the Enable Master Address Validation is Enabled (Checked).
The valid range is 0 to 65519. Default value is 0.
Master IP Address0
This value is used to:
• validate Master IP address when the Enable Access Control is Enabled
(Checked)
• send Unsolicited Response when Unsolicited Response functionality is
enabled. An Unsolicited Response is sent out to the DNP3 Master having
this address.
The valid value is an IP address. Default value is 0.0.0.0.
Master IP Address1, Master IP Address2, Master IP Address3, Master IP
Address4
This value is used for validation of the Master IP address when the Enable Access
Control is Enabled (Checked). This value is only valid when the Enable Access
Control is Enabled (Checked).
The valid value is an IP address. Default value is 0.0.0.0.
Remote TCP Port Number
This value is used to configure Master TCP Port Number for Unsolicited
Response.
The valid range is 0 to 65535. Default value is 20000.
Remote UDP Port Number for Initial Unsolicited
This value is used to configure Master UDP Port Number for Initial Unsolicited
Response if the parameter End Point Type is selected as Datagram Only.
The valid range is 0 to 65535. Default value is 20000.
Remote UDP Port Number
This value is used to configure Master UDP Port Number if the parameter End
Point Type is selected as Datagram Only.
The valid range is 0 to 65535. Default value is 20000.