Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
267
MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F
Disable Change of State Event: Setting this parameter suppresses the events
generated by any Event Occurrence Condition.
Event Occurrence Condition: The conditions of Data Set Event for each Data
Set Descriptor can be configured by Data Set Event Occurrence Condition
0/1/2/3 in the DNP3 Data Set Descriptors Object File. When one of the values
that are pointing to the Event Occurrence Condition 0/1/2/3 are changed or the
criteria are met, the MicroLogix 1400 generates a Data Set Event, retrievable
using the object g88v1.
This table shows the supported conditions for Point Addressing. Double-click
each case element to edit it.
Point Addressing under Event Occurrence Conditions: Valid selections are
shown below.
Note that a Data Set event can consume any number of event buffers, depending
on the Data Set configuration. This is only applicable to Data Set events. The
event for other objects consumes a single event buffer. When using Data Set
events, increase the number of events in the DNP3 Slave configuration.
Point Address Type
Point Type
Point Index
Event Occurence Condition
Standard DNP3 Point
NONE : No point type is
associated.
0
No Event is generated.
BI : Binary input
0 to 4095
When the Point Type and Point Index are pointing
a specific point, if the value of the point is
changed, an event is generated.
B2I : Double-bit input
0 to 2047
CI : Counter
0 to 511
AI : Analog input
0 to 767
BCD : BCD point
0 to 255
Reserved for others.
Reserved for others.
No Event is generated.