Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual
Page 312

272
Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
Appendix F MicroLogix 1400 Distributed Network Protocol (DNP3)
There are some rules for the Object flag set or clear for each bit by the controller.
The rules below are also applied to Event data.
• When the controller is in Non-Executing mode, the object flag is always all
0.
• When the controller is in Executing mode and there is no configuration
file, only the Online flag in the object flag is set.
• When the controller is in Executing mode and there is a configuration file,
the flags in the object flag are set according to the upper byte of the
configuration files.
Object Flags for Binary Input
Bit Offset
Name
Description
0
ONLINE
In Series A controllers:
0 when the controller is or was in Non-Execting mode.
1 when the controller is or was in Executing mode.
In Series B controllers:
0 when the controller is or was in Non-Execting mode.
1 when the controller is or was in Executing mode and the configuration file does not
exist. May be 1 when the controller is or was in Executing mode and the configuration
file exists.
1
RESTART
Always 0. Not used.
2
COMM_LOST
Always 0. Not used.
3
REMOTE_FORCED
Always 0. Not used.
4
LOCAL_FORCED
Always 0. Not used.
5
CHATTER_FILTER
Always 0. Not used.
6
reserved
Always 0. Not used.
7
STATE
Reflects point state of Binary Input point.
Object Flags for Double Binary Input
Bit Offset
Name
Description
0
ONLINE
In Series A controllers:
0 when the controller is or was in Non-Execting mode.
1 when the controller is or was in Executing mode.
In Series B controllers:
0 when the controller is or was in Non-Execting mode.
1 when the controller is or was in Executing mode and the configuration file does not
exist. May be 1 when the controller is or was in Executing mode and the configuration
file exists.
1
RESTART
Always 0. Not used.
2
COMM_LOST
Always 0. Not used.
3
REMOTE_FORCED
Always 0. Not used.
4
LOCAL_FORCED
Always 0. Not used.
5
CHATTER_FILTER
Always 0. Not used.
6
STATE
Reflects point state of Double-Bit Binary Input point. Double-bit LSB.
7
STATE
Reflects point state of Double-Bit Binary Input point. Double-bit MSB