Node Address
This value is a node address of this DNP3 Slave.
The valid range is 0 to 65519.
Default value is 1.
Baud
The selections can be "38.4 K", "19200", "9600", "4800", "2400", "1200", "600", and
"300".
Default selection is "19200".
Parity
The selections can be "NONE", "EVEN", and "ODD". Default selection is
"NONE".
Stop Bits
The selections can be "1", "1.5", and "2".
Default selection is "1".
Enable Master Address Validation
Valid selections are Enabled(Checked) and Disabled(Unchecked). Default value
is Disabled (Unchecked).
When the selection is Disabled(Unchecked), the MicroLogix 1400 accepts the
requests from any DNP3 Master.
When the selection is Enabled(Checked), the MicroLogix 1400 accepts the
requests only from the DNP3 Master which is configured in the Master Node0 to
Master Node4. The maximum number of Master Node Addresses for the Master
Address Validation is 5.
Enable Self-Address
Valid selections are Enabled(Checked) and Disabled(Unchecked). Default value
is Disabled (Unchecked).
When this bit is Disabled(Unchecked), any packets which contain the
destination address 65532(FFFCh) are ignored.
When this bit is Enabled(Checked), any packets which contain the destination
address 65532(FFFCh) are accepted and processed.