Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual
Page 313
Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
273
MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F
Object Flags for Binary Output
Bit Offset
Name
Description
0
ONLINE
0 when the controller is or was in Non-Executing mode.
1 when the controller is or was in Executing mode and the configuration file does not exist.
May be 1 when the controller is in Executing mode and the configuration file exists.
1
RESTART
Always 0. Not used.
2
COMM_LOST
Always 0. Not used.
3
REMOTE_FORCED
Always 0. Not used.
4
LOCAL_FORCED
Always 0. Not used.
5
reserved
Always 0. Not used.
6
reserved
Always 0. Not used.
7
STATE
Reflects point state of Binary Output point.
Object Flags for Counter
Bit Offset
Name
Description
0
ONLINE
0 when the controller is or was in Non-Executing mode.
1 when the controller is or was in Executing mode and the configuration file does not
exist.
May be 1 when the controller is in Executing mode and the configuration file exists.
1
RESTART
0 when the controller is or was in Non-Executing mode.
0 when the controller is or was in Executing mode and the configuration file does not
exist.
May be 1 when the controller is in Executing mode and the configuration file exists.
2
COMM_LOST
3
REMOTE_FORCED
4
LOCAL_FORCED
5
ROLLOVER
6
DISCONTINUITY
7
reserved
Object Flags for Analog Input
Bit Offset
Name
Description
0
ONLINE
0 when the controller is or was in Non-Executing mode.
1 when the controller is or was in Executing mode and the configuration file does not
exist.
May be 1 when the controller is in Executing mode and the configuration file exists.
1
RESTART
0 when the controller is or was in Non-Executing mode.
0 when the controller is or was in Executing mode and the configuration file does not
exist.
May be 1 when the controller is in Executing mode and the configuration file exists.
2
COMM_LOST
3
REMOTE_FORCED
4
LOCAL_FORCED
5
OVER_RANGE
6
REFERENCE_ERR
7
reserved