Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual
Page 177
Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
135
Specifications Appendix A
Hazardous environment class
For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
Hazardous Location, Class I, Division 2 Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213,
ANSI/ISA-12.12.01)
For all other modules:
Hazardous Location, Class I, Division 2 Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213) for all
modules
Radiated and conducted emissions
EN50081-2 Class A
Electrical/EMC:
The module has passed testing at the following levels:
ESD immunity
For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-2: 4 kV contact, 8 kV air, 4 kV indirect
For all other modules:
IEC1000-4-2: 4 kV contact, 8 kV air, 4 kV indirect
Radiated RF immunity
For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-3: 10V/m, 80…2700 MHz, 80% amplitude modulation
For all other modules:
IEC1000-4-3: 10 V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier for all
modules
EFT/B immunity
For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-4: 2 kV, 5 kHz on signal ports
For all other modules
IEC1000-4-4: 2 kV, 5 kHz
Surge transient immunity
For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-5: 2 kV common mode, 1 kV differential mode
For all other modules
IEC1000-4-5: 2 kV common mode, 1 kV differential mode
Conducted RF immunity
For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-6: 10V, 0.15…80 MHz
(2)
For all other modules:
IEC1000-4-6: 10V, 0.15…80 MHz
(2)
(1) For module-specific operating temperature range, refer to the Installation Instructions for the specific module.
(2) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30…1000 MHz.
General Specifications
Specification
Value
Input Specifications
Specification
1762-IA8
1762-IQ8
1762-IQ16
1762-IQ32T
1762-IQ8OW6
Shipping weight, approx.
(with carton)
209 g (0.46 lbs.)
200 g (0.44 lbs.)
230 g (0.51 lbs.)
200g (0.44 lbs.)
280g (0.62 lbs.)
Voltage category
100/120V AC
24V DC (sink/source)
(1)
24V DC (sink/source)
(1)
24V DC
(sink/source)
(1)
24V DC (sink/source)
(1)
Operating voltage range
79V AC…132V AC at
47 Hz…63 Hz
10…30V DC at 30 °C
(86 °F)
10…26.4V DC at 55 °C
(131 °F)
10…30V DC
10…26.4V DC
(2)
10…30V DC
(24 points) at 30 °C
(86 °F)
10…26.4V DC
(23 points)at 60 °C
(140 °F)
10…30V DC at 30 °C
(86 °F)
10…26.4V DC at
65 °C (149 °F)
Number of inputs
8
8
16
32
8
Bus current draw, max.
50 mA at 5V DC
(0.25W)
50 mA at 5V DC
(0.25W)
70 mA at 5V DC
(0.35W)
(3)
170 mA at 5V DC
0 mA at 24V DC
110 mA at 5V DC
80 mA at 24V DC