Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual
Page 49
Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
35
Wire Your Controller Chapter 3
Solid wire
Cu-90
⋅C (194⋅F)
14…22 AWG
Stranded wire
Cu-90
⋅C (194⋅F)
16…22 AWG
Wiring torque = 0.791Nm (7 in-lb) rated.
Wire Types and Sizes
Output Terminal Grouping
Controllers
Output Group
Description
Outputs
Voltage Terminal
Output Terminal
1766-L32BWA
1766--L32BWAA
Group 0
Isolated relay output
VAC/DC0
OUT 0
Group 1
Isolated relay output
VAC/DC1
OUT 1
Group 2
Isolated relay output
VAC/DC2
OUT 2
Group 3
Isolated relay output
VAC/DC3
OUT 3
Group 4
Isolated relay output
VAC/DC4
OUT 4, OUT 5
Group 5
Isolated relay output
VAC/DC5
OUT 6, OUT 7
Group 6
Isolated relay output
VAC/DC6
OUT 8…11
1766-L32AWA
1766-L32AWAA
Group 0
Isolated relay output
VAC/DC0
OUT 0
Group 1
Isolated relay output
VAC/DC1
OUT 1
Group 2
Isolated relay output
VAC/DC2
OUT 2
Group 3
Isolated relay output
VAC/DC3
OUT 3
Group 4
Isolated relay output
VAC/DC4
OUT 4, OUT 5
Group 5
Isolated relay output
VAC/DC5
OUT 6, OUT 7
Group 6
Isolated relay output
VAC/DC6
OUT 8…11
1766-L32BXB
1766-L32BXBA
Group 0
Isolated relay output
VAC/DC0
OUT 0
Group 1
Isolated relay output
VAC/DC1
OUT 1
Group 2
FET output
VDC2/COM 2
OUT 2…7
Group 3
Isolated relay output
VAC/DC3
OUT 8
Group 4
Isolated relay output
VAC/DC4
OUT 9
Group 5
Isolated relay output
VAC/DC5
OUT 10, OUT 11
WARNING: If you connect or disconnect wiring while the
field-side power is on, an electrical arc can occur. This could cause
an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.
WARNING: The local programming terminal port is intended for
temporary use only and must not be connected or disconnected
unless the area is free of ignitable concentrations of flammable
gases or vapors.