Status indicators on the lcd – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual
Page 198

158
Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
Appendix C Troubleshooting Your System
Status Indicators on the LCD
Figure 4 - Status Indicators on the LCD
FAULT
off
No fault detected
red flashing
Application fault detected
red
Controller hardware faulted
FORCE
off
No forces installed
amber
Forces installed
amber flashing
Forces installed in force files but forcing is disabled.
Status Indicators on the LCD
Indicator
Color
Indicates
COMM 0
off
(empty rectangle)
Not transmitting via RS-232/485 port (Channel 0)
on
(solid rectangle)
Transmitting via RS-232/485 port (Channel 0)
COMM 1
off
(empty rectangle)
Not transmitting via Ethernet port (Channel 1)
on
(solid rectangle)
Transmitting via Ethernet port (Channel 1)
COMM 2
off
(empty rectangle)
Not transmitting via RS-232 port (Channel 2)
on
(solid rectangle)
Transmitting via RS-232 port (Channel 2)
DCOMM
(1)
off
(empty rectangle)
Configured communications (Channel 0)
on
(solid rectangle)
Default communications (Channel 0)
BAT. LO
off
(empty rectangle)
Battery level is acceptable
on
(solid rectangle)
Battery low
U-DISP
off
(empty rectangle)
Default display mode
on
(solid rectangle)
Customized display mode
Controller LED Indicators
LED
Color
Indicates
CO
M
M
0
COMM1 DCOM
M
BA
T. LO
U-
DI
SP
COM
M
2