Grounding, Mechanical configuration, Figure c.1 – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 200: Figure c.2, Rfi filter grounding

C–4
CE Conformity
Grounding
RFI Filter Grounding
Important: Using the optional RFI filter may result in relatively high
ground leakage currents. Surge suppression devices are
also incorporated into the filter. Therefore, the filter must
be permanently installed and solidly grounded (bonded) to
the building power distribution ground. Ensure that the
incoming supply neutral is solidly connected (bonded) to
the same building power distribution ground.
Grounding must not rely on flexible cables and should not
include any form of plug or socket that would permit
inadvertent disconnection. Some local codes may require
redundant ground connections. The integrity of all
connections should be periodically checked.
Mechanical Configuration
1
Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with equivalent attenuation. Shielding/
armor must be bonded to the metal bottom plate. See requirements 5 & 6 on page
2
Refer to the Filter Selection table on page
for frame references and corresponding catalog numbers.
To Motor
1
Cable Supplied with Filter
1
Conduit
1
To Motor
1
Three-Phase Input
1
Access
Panel
Flat Washer
Star Washers
Bolt
Bolt
Important: Drive and filter must be
mounted to a common back plane
with a positive electrical bond and in
close proximity to one another.
Important: A positive electrical bond must be
maintained between drive and filter at all 4
corners. Star washers can be eliminated
if a positive electrical bond is
assured.
Three-Phase
Input
1
Figure C.1 (Side-by-Side)
1336
PLUS
II
Frames A1 - A3
2
Figure C.2 (One Assembly)
1336
PLUS
II
Frames A4, B & C
2