Slip comp gain, Run on power up, Reset/run tries – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 102: Reset/run time, S curve enable, S curve time

6–20
Programming
[Slip Comp Gain]
This parameter is the gain for the slip compensation and
adjusts the recovery rate after a load change.
Parameter Number
195
Parameter Type
Read and Write
Display Units / Drive Units
None
Factory Default
1
Minimum Value
1
Maximum Value
40
[Run On Power Up]
This parameter enables the function that allows the drive
to automatically restart on Power Up. This parameter re-
quires that a two wire control scheme be installed at TB3
and that a valid start contact be present. Refer to Input
Mode Selection in Chapter 2.
Parameter Number
14
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1
[Reset/Run Tries]
This value sets the maximum number of times the drive
attempts to reset a fault and restart before the drive issues
a “Max Retries Fault”. See Chapter 7 for a list of resettable
faults.
Parameter Number
85
Parameter Type
Read and Write
Display Units / Drive Units
1 Try / Tries
Factory Default
0
Minimum Value
0
Maximum Value
9
[Reset/Run Time]
This value sets the time between restart attempts when
[Reset/Run Tries] is set to a value other than zero.
Parameter Number
15
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Second / Seconds x 100
Factory Default
1.0 Sec
Minimum Value
0.5 Sec
Maximum Value
30.0 Sec
[S Curve Enable]
This parameter enables the fixed shape S curve accel/
decel ramp. Programmed accel/decel times are doubled if
[S Curve Time] is set to “0”. An adjustable S curve will be
created if [S Curve Time] is greater than zero.
Parameter Number
57
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1
[S Curve Time]
This creates an adjustable s curve ramp. If S Curve Time
is < the programmed accel/decel time, the actual ramp will
be the sum of the two. If S Curve Time is
≥ the programmed
accel/decel times, a fixed S curve will be created whose time
is double the programmed accel/decel time.
Parameter Number
56
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Second / Seconds x 10
Factory Default
0.0 Sec
Minimum Value
0.0 Sec
Maximum Value
1800.0 Sec
ATTENTION: This parameter may only be used as outlined in NFPA79, “Under
Voltage Protection.” Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application.
!