Drive alarm 2, Latched alarms 1, Latched alarms 2 – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 119: Input status, Diagnostics
Programming
6–37
[Drive Alarm 2]
This parameter displays which alarm
condition is present when bit 6 of [Drive
Status 1] is high. Refer to Chapter 7 for
further alarm information.
A Status description (bit ENUM) is
displayed on line 1 (except Series A
HIMs below version 3.0).
Parameter Number
269
Parameter Type
Read Only
[Latched Alarms 1]
This parameter “stores” the [Drive Alarm
1] indications (see above). Bits will re-
main set (high/1), even if the alarm
condition no longer exists. The bit(s)
must be programmed to zero to release
the stored indications.
A Status description (bit ENUM) is dis-
played on line 1 (except Series A HIMs
below version 3.0).
Parameter Number
205
Parameter Type
Read and Write
[Latched Alarms 2]
This parameter “stores” the [Drive Alarm
2] indications (see above). Bits will re-
main set (high/1), even if the alarm
condition no longer exists. The bit(s)
must be programmed to zero to release
the stored indications.
A Status description (bit ENUM) is
displayed on line 1 (except Series A
HIMs below version 3.0).
Parameter Number
270
Parameter Type
Read and Write
[Input Status]
This parameter displays the on/off status of inputs 1-8 at
TB3 if an optional interface card is installed.
A Status description (bit ENUM) is displayed on line 1 (ex-
cept Series A HIMs below version 3.0).
Parameter Number
55
Parameter Type
Read Only
Motor Therm
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Bit 14
Unused
Encoder Loss
Load Loss
Enc Cnt Max
Enc Cnt Set
Voltage Check
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor Stalled
Ground Warning
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Mtr Overload
Sync Loss
Bit 14
Hardware Current Limit
Motoring Current Limit
Motor OL Trip
Auto Reset
Phase Loss
Heatsink Temp
Auxiliary Input
4-20 mA Loss
Motor Therm
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Bit 14
Unused
Encoder Loss
Load Loss
Enc Cnt Max
Enc Cnt Set
Voltage Check
Bit 7 Bit 6
Bit 5 Bit 4 Bit 3
Bit 2 Bit 1 Bit 0
Input 1 - TB3-19
Input 2 - TB3-20
Input 4 - TB3-23
Input 3 - TB3-22
Input 5 - TB3-24
Input 6 - TB3-26
Input 8 - TB3-28
Input 7 - TB3-27