Dig out freq, Dig out current, Dig out torque – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 110: Dig at temp, Digital i/o
![background image](/manuals/578476/110/background.png)
6–28
Programming
[CR1 Out Select]
[CR2 Out Select]
[CR3 Out Select]
[CR4 Out Select]
This parameter sets the condition that changes the state
of the output contacts at TB2 terminals 10 & 11 (CR1), 11
& 12 (CR2), 13, 14, 15 (CR3) and 16, 17, 18 (CR4).
A change of state may mean energize or de-energize the
relay, since some relays may energize on power-up and
de-energize when the selected condition occurs.
A red LED located on the Main Control Board indicates the
status of the CR3 contact. The LED will illuminate when
the contacts at terminals 13 & 14 of TB2 are closed and
terminals 14 & 15 are open.
Parameter Number
158, 174-176
Parameter Type
Read and Write
Factory Default
“At speed” CR1
“Running” CR2
“Fault” CR3
“Alarm” CR4
Units
Display Drive
“Fault” 0
Any fault
“Alarm” 1
Any unmasked alarm
“Running” 2
Outputting frequency
“At Speed” 3
Output = command
“At Freq” 4
Requires value in [Dig Out Freq]
“At Current” 5
Requires value in [Dig Out Curr]
“At Torque” 6
Requires value in [Dig Out Torque]
“Current Lmt” 7
In overload
“Mtr Overload” 8
At present levels O.L. will occur
“Line Loss” 9
Line loss in progress
“Drive Power” 10 Full input volts present, bus charged
“Drive Ready” 11 All necessary commands present
“Forward Run” 12 Forward direction
“Reverse Run” 13 Reverse direction
“Braking” 14 DC brake mode (stopping or holding)
“Economize” 15 Auto economizer active
“Auto Reset” 16 Attempt to reset fault & restart drive
“At Temp” 17 Requires value in [Dig At Temp]
“PI Max Error” 18 Requires value in [PI Max Error]
“Remote” 19 Set by [Remote CR Output]
Firmware 5.001 & later
“Step Logic” 20 Set by [SLx Step Setting] SL Output
[Dig Out Freq]
This value sets the trip point for any digital output relay
(CR1-4 – see above) that is programmed to “At
Frequency”. The relay will be energized when the value is
exceeded.
Parameter Number
159
Parameter Type
Read and Write
Display Units / Drive Units
0.01 Hertz / 32767 = Max Freq
Factory Default
0.00 Hz
Minimum Value
0.00 Hz
Maximum Value
Programmed [Maximum Freq]
[Dig Out Current]
This value sets the trip point for any digital output relay
(CR1-4 – see above) that is programmed to “At Current”.
The relay will be energized when the value is exceeded.
Parameter Number
160
Parameter Type
Read and Write
Display Units / Drive Units
0% / 4096 = 100% of Drive Rated Amps
Factory Default
0 %
Minimum Value
0 %
Maximum Value
200 %
[Dig Out Torque]
This value sets the trip point for any digital output relay
(CR1-4 – see above) that is programmed to “At Torque”.
The relay will be energized when the value is exceeded.
Parameter Number
161
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Amps / 4096 = Rated Torque Amps
Factory Default
0.0 Amps
Minimum Value
0.0 Amps
Maximum Value
200% of [Rated Amps]
[Dig At Temp]
This parameter sets the heatsink temperature trip point for
any digital output relay (CR1-4 – see above) that is
programmed to “At Temp.” The relay will be energized
when this value is exceeded. See also [Drive Status 2], bit
13 and [Drive Alarm 1], bit 10.
Parameter Number
267
Parameter Type
Read and Write
Display Units / Drive Units
1
° C / Deg. C
Factory Default
120
° C
Minimum Value
0
Maximum Value
255
° C