Fstart forward, Fstart reverse, Lloss restart – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 104: Line loss mode, Feature select
![background image](/manuals/578476/104/background.png)
6–22
Programming
[FStart Forward]
This value sets the frequency at which the forward speed
search begins. If this value exceeds [Maximum Freq],
speed search will begin at [Maximum Freq]. Forward
search ends at zero Hertz or when motor speed is found.
Parameter Number
156
Parameter Type
Read and Write
Display Units / Drive Units
1 Hertz / Hertz
Factory Default
60 Hz
Minimum Value
0 Hz
Maximum Value
400 Hz
[FStart Reverse]
This value sets the frequency at which the reverse speed
search begins. If this value exceeds [Maximum Freq],
speed search will begin at [Maximum Freq]. Reverse
search ends at zero Hertz or when motor speed is found.
Parameter Number
157
Parameter Type
Read and Write
Display Units / Drive Units
1 Hertz / Hertz
Factory Default
0 Hz
Minimum Value
0 Hz
Maximum Value
400 Hz
[LLoss Restart]
This parameter selects the reconnect mode after recovery
from a line loss condition.
Parameter Number
228
Parameter Type
Read and Write
Factory Default
“Track Volts”
Units
Display Drive
“Speed Search” 1
Frequency sweep
“Use Encoder” 2
Read feedback
“Track Volts” 3
Read motor volts
Firmware 5.001 & later
“Speed Srch 10s” 4
Frequency sweep takes 10 seconds
Firmware 5.001 & later
“Speed Srch 20s” 5
Frequency sweep takes 20 seconds
Firmware 5.001 & later
“Speed Srch 40s” 6
Frequency sweep takes 40 second
Drive Units=“4” Firmware 4.001 & before “Last Speed” 7
Start at last output
[Line Loss Mode]
This parameter sets the drive reaction to a loss of input
voltage and is often referred to as Inertia Ride Through.
If the drive is used to determine loss of AC input (as op-
posed to an external device), it will monitor the falling DC
bus voltage. When Vbus falls below 85% of nominal, a
“line loss” condition is issued and an alarm bit is set.
The line loss mode selected, along with [Line Loss Fault]
and [Low Bus Fault] will determine the drives response to
a loss of input.
• With this parameter set to “LoBus>Off” and . . .
[Line Loss Fault] is . . .
- Enabled a fault is issued 0.5 seconds after a “line
loss” condition.
- Disabled a fault will not be issued.
[Low Bus Fault] is . . .
- Enabled a fault is issued at the bus undervoltage
trip level.
- Disabled a fault will not be issued.
• With this parameter set to “LoBus>Decel” and [Line
Loss Fault] & [Low Bus Fault] are disabled – the drive
will decelerate the output frequency following motor
speed to create a regenerative condition that maintains
Vbus at 85% nominal. The amount of available me-
chanical energy determines the length of “ride
through.”
If this parameter = “LoBus>Off,” then [LLoss Restart] de-
termines the reconnect scheme for the motor. If this
parameter is set to “LoBus>Decel,” no reconnect scheme
is required.
Parameter Number
256
Parameter Type
Read/Write
Factory Default
“LoBus>Off”
Units
Display Drive
“LoBus>Off” 0
Turn off output on –15% Vbus
“Input>Off” 1
Not functional at time of printing.
Turns off output on
High Speed Input = True
“LoBus>Decel” 2
Regulates Vbus using deceleration
Active on –15% Vbus
“Input>Decel” 3
Not functional at time of printing.
Regulates Vbus using deceleration
Active on High Speed Input = True