Electrical, Control, Input/output ratings – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 158: Each 1336
![background image](/manuals/578476/158/background.png)
A–2
Specifications and Supplemental Information
Electrical
Input Data
Voltage Tolerance:
–10% of minimum, +10% of maximum.
Frequency Tolerance:
47-63 Hz.
Input Phases:
Three-phase input provides full rating for all drives.
Single-phase operation is possible for A & B Frame drives
at a derating of 50%.
Displacement Power Factor
A1-A3 Frame Drives:
0.80 standard, 0.95 with optional inductor.
A4 Frame & Up Drives:
0.95 standard.
Efficiency:
97.5% at rated amps, nominal line volts.
Max. Short Circuit Current Rating: Installations per U.S. NEC/UL/CSA
Using Specified Fuses
200,000A
Using Specified HMCP Breakers Per “Max. Short Circuit Amps” column in
,
specific to each rating.
Using Specified HMCP Breakers
with Current Limiter Option
200,000A
IEC Installations per IEC947
Using Specified 140 Devices
Per “Rated Service Short Circuit Capability” column in
specific to each rating.
Control
Method:
Sine coded PWM with programmable carrier frequency. Ratings
apply to all drives (refer to the Derating Guidelines on page
).
A & B Frame Drives
2-8 kHz. Drive rating based on 4 kHz (see pg.
for frame info).
C & D Frame Drives
2-6 kHz. Drive rating based on 4 kHz (see pg.
for frame info).
E Frame Drives & Up
2-6 kHz. Drive rating based on 2 kHz (see pg.
for frame info).
Output Voltage Range:
0 to rated voltage.
Output Frequency Range:
0 to 400 Hz.
Frequency Accuracy
Digital Input:
Within
±0.01% of set output frequency.
Analog Input:
Within
±0.4% of maximum output frequency.
Selectable Motor Control:
Sensorless Vector with full tuning. Standard V/Hz with full custom
capability.
Accel/Decel:
Two independently programmable accel and decel times. Each time
may be programmed from 0 - 3600 seconds in 0.1 second increments
1
.
Intermittent Overload:
Constant Torque - 150% of rated output for 1 minute.
Variable Torque - 115% of rated output for 1 minute.
Current Limit Capability:
Proactive Current Limit programmable from 20 to 160% of rated
output current. Independently programmable proportional and
integral gain.
Inverse Time Overload Cap.
Class 10 protection with speed sensitive response. Investigated by U.L.
to comply with N.E.C. Article 430. U.L. File E59272, volume 4/6.
1
0.1 second increments using a HIM or 0.01 with serial communications.
Input/Output Ratings
Each 1336
PLUS
II
Drive has constant and variable torque capabil-
ities. The listings on the next page provide input & output current and
kVA ratings.
Note: Drive ratings are at nominal values. See Derating Guidelines on
page
.