Alarms, Alarms –9 – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 155
Troubleshooting
7–9
Alarms
presents a listing and description of the drive alarms. Alarm
status can be viewed by selecting the [Drive Alarm 1/2] parameter.
An active alarm will be indicated by its corresponding bit being set to
high (1). Any high bit (1) can energize CR1-4 (if programmed).
Table 7.D
Alarm Conditions
Parameter Name [Drive Alarm 1]
Parameter Number 60
Parameter Type
Read Only
Parameter Name [Drive Alarm 2]
Parameter Number 269
Parameter Type
Read Only
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor Stalled
Ground Warning
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Mtr Overload
Sync Loss
Bit 14
Hardware Current Limit
Motoring Current Limit
Motor OL Trip
Auto Reset
Phase Loss
Heatsink Temp
Auxiliary Input
4-20 mA Loss
Motor Therm
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Bit 14
Unused
Encoder Loss
Load Loss
Enc Cnt Max
Enc Cnt Set
Voltage Check
Alarm
Bit
Alarm Name
Description
[Drive
Alarm 1]
0
Bus Charging
Precharge of DC bus capacitors is in progress.
1
Hardware Current Limit
An alarm will be issued when 220% of drive rated current is reached.
2
Motoring Current Limit
The value programmed for [Current Limit] has been exceeded while in the motoring mode.
3
Regenerating Current Limit An alarm will be issued when the value set for [Current Limit] has been exceeded while the motor is
regenerating.
4
Regenerating Voltage Limit Bus limiting is active.
5
Line Loss In Progress
An alarm will be issued when the AC incoming voltage drops below 20% of input or a 150 volt drop
takes place.
6
Mtr Overload
At the present value of output amps, a motor overload trip will eventually occur.
7
Motor Stalled
Drive output frequency folds to 0 Hz and current limit is still active or voltage limit will not allow decel.
8
Ground Warning
Ground current exceeds 2 amperes.
9
Auxiliary Input
Input circuit is open.
10
Heatsink Temp
Temperature of drive heatsink has exceeded its limit.
11
Sync Loss
Synchronous motor not at synchronous speed.
12
Phase Loss
The DC bus ripple has exceeded the level in [Phase Loss Level].
13
4-20mA Loss
4-20mA signal lost.
14
Motor OL Trip
This bit will be high when the motor overload function has integrated high enough to cause a motor
overload fault. This bit is active regardless of the [Motor Overload] state (enabled/disabled).
15
Auto Reset
Drive is attempting to reset a fault using [Reset/Run Tries] & [Reset/Run Time].