beautypg.com

Anlg out 0 sel] [anlg out 1 sel, Anlg out 0 offset] [anlg out 1 offset, Anlg out 0 abs] [anlg out 1 abs – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 113: Anlg out 0 lo] [anlg out 1 lo, Anlg out 0 hi] [anlg out 1 hi, Slot a option] [slot b option, Analog i/o

background image

Programming

6–31

Analog I/O

[Anlg Out 0 Sel]
[Anlg Out 1 Sel]

This parameter selects the source value that will drive the
analog output. This output is intended for metering only
and should not be used as process control feedback.

Parameter Number

25, 274

Parameter Type

Read and Write

Factory Default

“Frequency” Out 0

“Current” Out 1

Units

Display Drive Range

“Frequency” 0

Zero to programmed [Maximum Freq]

“Current” 1

Zero to 200% of Drive Rated

“Torque” 2

Zero to 200% of Drive Rated

“Power” 3

Zero to 200% of Drive Rated

“Voltage” 4

Zero to 200% of Drive Rated

“% Motor OL” 5

Zero to 200% of Drive Rated

“% Drive OL” 6

Zero to 200% of Drive Rated

“Encoder” 7

See [Encoder Freq]

“Speed Error” 8

See [Speed Error]

“PI Reference” 9

See [PI Reference]

“PI Feedback” 10

See [PI Feedback]

“PI Error” 11

See [PI Error]

“PI Output” 12

See [PI Output]

[Anlg Out 0 Offset]
[Anlg Out 1 Offset]

This parameter enables the voltage or current offset for the
analog output. This internal value offsets 0-20mA to 4-
20mA and 0-10V to 2-10V.

Parameter Number

154, 278

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

[Anlg Out 0 Abs]
[Anlg Out 1 Abs]

This parameter selects whether a signed value or absolute
value is used for analog out.

Parameter Number

233, 277

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

[Anlg Out 0 Lo]
[Anlg Out 1 Lo]

Sets the percentage of voltage or current output that rep-
resents the low end of the “Range” listed in [Anlg Out Sel].

Parameter Number

234, 275

Parameter Type

Read and Write

Display Units / Drive Units

0.1% / 4096 = 100%

Factory Default

0.0%

Minimum Value

–300.0%

Maximum Value

+300.0%

[Anlg Out 0 Hi]
[Anlg Out 1 Hi]

Sets the percentage of voltage or current output that rep-
resents the high end of the “Range” listed in [Anlg Out
Sel].Example: To get 150% of current to equal 10V/20mA,
set this parameter to 150%.

Parameter Number

235, 276

Parameter Type

Read and Write

Display Units / Drive Units

0.1% / 4096 = 100%

Factory Default

100.0%

Minimum Value

–300.0%

Maximum Value

+300.0%

[Slot A Option]
[Slot B Option]

Displays the catalog number of the analog I/O option board
currently installed in slots A and/or B.

Parameter Number

252, 253

Parameter Type

Read Only

Factory Default

“Standard”

Units

Display Drive

“Standard” 0

“LA1” 1
“LA2” 2
“LA3” 3
“LA4” 4
“LA5” 5
“LA6” 6
“LA7” 7

“Undefined” 8

Board not recognized