Chapter 3
Hardware Description
40 – 100 HP, 230VAC
75 – 200 HP, 460VAC
3-3
Armature Bridge Components
A general description of the components in the armature bridge (Figures
3.2 and 3.3) and their operation is detailed here:
AC Line Reactor – When connecting the drive directly to the main
distribution system an AC line reactor must be used to guard against
system disturbance.
When an isolation transformer matched to the unit rating is used, an AC
line reactor is not required.
Fast acting semiconductor fuses F1, F2 and F3 are standard on all drives.
Synchronization – The three-phase input to the drive is tapped and fused
using fuses F4, F5 and F6 (Fig. 3.2) and enters the feedback board. The
feedback board scales down the voltage before being sent to the power
stage interface where it is used to develop the synchronizing information to
be used by the Main Control Board.
AC Current Feedback – Current Transformers ACT-1 and ACT-2
(Figure 3.2) are used to provide current feedback information to the
feedback board. The feedback board rectifies the three-phase feedback and
scales the DC voltage before being sent to the power stage interface. The
DC voltage representing the current feedback is passed directly through the
power stage interface and sent to the main control board.
Figure 3.2
Armature Bridge Components (INPUT)
To Feedback Board
TB1-11, 13, 15 Figure 3.5
To Feedback Board
L1
L2
L3
F1
F2
F3
To TB1
Fig. 3.4
Isolation
Transformer
or Line
Reactor