Parameter 610 – Rated Motor Voltage [Rated Motor Volt]

Internal units : volts x 10
Programming Terminal units: VOLTS
Minimum Value: 75
Maximum Value: 850
Default Value: 240
Function: Torque Control

Description : Nameplate rated motor voltage. This should be the
measured armature voltage when the motor is running at base speed
with rated field current.
Note: This parameter WILL NOT limit motor voltage to the value
entered. Complete parameter set-up (Chapter 8) is required to
prevent overvoltage conditions from occuring.

Parameter 611 – Motor Armature Full Load Amp [Motor Arm
FLA]

Internal units : Amps x 10
Programming Terminal units: AMPS
Minimum Value: 0.1
Maximum Value: 32767
Default Value: 0.2

Description : Nameplate rated motor armature current

Parameter 612 – Rated Field Motor Current [Rate Fld Mtr Cur]

Internal units : Amps x 10
Programming Terminal units: AMPS
Minimum Value: 0.1
Maximum Value: 32767
Default Value: 0.1
Description : Nameplate rated motor field current.

Parameter 613 – Motor Inertia [Motor Inertia]

Internal units : seconds x 100
Programming Terminal units: Seconds
Minimum Value: 0.01
Maximum Value: 10.00
Default Value: 6.0
Description : This parameter represents the time, in seconds, taken
for the uncoupled motor to accelerate from zero speed to base speed
with rated motor armature and field current applied.