beautypg.com

Rockwell Automation 1395 Digital DC Drive FRN 5-10.10/9.30 User Manual

Page 155

background image

Chapter 6
Installation

6-31

24VDC Connection/Digital Input – Sizing of the power supply is based
on the number of input and output selections. Figure 6.18 shows the
typical connection of the digital input using the external power supply.

Analog Input – Velocity and Trim Reference. Connections for the
velocity and trim reference inputs can be for uni- or bi-directional
operation, using the internal drive

±

10VDC power supply (see Fig.6.19 ).

Figure 6.18
Typical 24VDC Digital Input Connections using External Power Supply

DIGITAL IN 2

47

48

49

50

51

TB3

DIGITAL COMMON

DIGITAL IN 1

DIGITAL IN 3

DIGITAL IN 4

Clear Faults*

Start*

Jog 2*

Stop*

24V DC Common

24V DC High

* External to the Drive

Figure 6.19
Typical Analog Input Connections

32

31

+

33

TB3

+10V DC P.S.

–10V DC P.S.

ANALOG INPUT

P.S. COMMON

Bi-directional Operation

IMPORTANT: Connect
shield to drive end only.
Other end is to be insu-
lated and left floating.

Reference*

2.5k Ohm

Minimum

32

31

+

33

TB3

+10V DC P.S.

–10V DC P.S.

ANALOG INPUT

P.S. COMMON

TB4 (TB-10 on 125-600 HP)

Uni-directional Operation

IMPORTANT: Connect
to either terminal 31 or
32, Not Both

Reference*

2.5k Ohm

Minimum

R

R

Forward

Reverse

R*

Reverse Relay

* External to the Drive

*

TB4 (TB-10 on 125-600 HP)