Rockwell Automation 1395 Digital DC Drive FRN 5-10.10/9.30 User Manual

Page 230

background image

Chapter 7

Programming Parameters

7-64

Parameter 726– SCR Overtemperature Delay [SCR Overtemp

Delay]

Internal units : Seconds x 10

Programming Terminal units: Seconds

Minimum Value: 0.1

Maximum Value: 3276.7

Default Value: 1.0

Description: This parameter specifies the length of time that the

heatsink overtemperature discrete input must be low before an SCR

overtemperature fault will be indicated.

Parameter 727– Stall Delay [Stall Delay]

Internal units : Seconds x 10

Programming Terminal units: Seconds

Minimum Value: 0

Maximum Value: 100.0

Default Value: 10.0

Description: This parameter specifies the length of time that the drive

must be in current limit and at zero speed before a stall fault will be

indicated.

Parameter 728 – AC Line Tolerance Delay [AC Line Tol Delay]

Internal units : Seconds x 10

Programming Terminal units: Seconds

Minimum Value: 0

Maximum Value: 1.0

Default Value: 0.1

Description: This parameter specifies the length of time that the

supply voltage is allowed to deviate by more than +15% or –20% of

the rated value (Parameter 617) before a voltage out of tolerance fault

will be indicated.

Parameter 729– Field Fault Threshold [Fld Flt Thresh]

Internal units : 4096 = 1000h = 1 PU = 100% rated motor field

current

Programming Terminal units: Percent rated field current

Minimum Value: 0%

Maximum Value: 100%

Default Value: 30%

Description: This parameter is used to set the threshold for activating

the motor field loss fault in the CP fault word (Parameter 101, bit 6).

Internally, if the field current reference (Parameter 117) is greater

than the field current threshold (Parameter 729) and the field current

feedback (Parameter 118) is less than 10% of threshold, a field loss

fault occurs. A value of zero disables the field loss fault detection.