Chapter 6
Installation

6-9

Figure 6.5
1395 Grounding Practices

TE

Discrete

Adapter Board

TE

Analog I/O

DC Tach

Remote

PLC

PLC I/O Link

GND

Next Rack

TB3

Conduit Ground

Insulated Signal Bus “TE”

Power Safety Ground “PE”

GND

L1 L2 L3

Transformer

Conduit Ground

Encoder

Encoder shield must not
be grounded at drive

Building steel or

substation ground

Conduit Ground

Building steel or

substation ground

Connect to adjacent building steel

(girder/joist) or a floor ground loop

Connect to earth ground such as a

dedicated ground rod or grid etc.

TE

PE

Ground

PE

Encoder

Encoder cable in steel conduit

(Grounded – wiring Class 8)

Encoder Grounding –

Motor Leads Not Grounded

(Wiring Class 3 or 4)

DC Tach

Tach cable in steel conduit

(Grounded – wiring Class 8)

DC Tach Grounding –

Motor leads Not Grounded

(Wiring Class 3 or 4)

Safety Ground to be Grounded by User

Indicates Chassis Ground

Signal Ground

Power Safety Ground

Node Adapter

Board (if used)

Power

Converter