Specifications – Rockwell Automation 1395 Digital DC Drive FRN 5-10.10/9.30 User Manual
Page 14

Chapter 1
Introduction, Inspection & Storage, and
Publication References
1-4
Specifications
Input Voltages –
Input Power –
Input Frequency –
Max Rate of Change of
Input Frequency –
Output Voltage –
Output Horsepower
(Continuous) –
Output Current–
Field Voltage–
Field Current–
Field Control–
Field Economy–
Armature Firing–
Output Waveform–
Controller Current
Output –
Armature Control –
150 – 460VAC +/– 10%, 3 phase
115VAC Control Power, +/– 10%, 1 phase
1.5 kVA to 660 kVA
50/60Hz +/– 3 Hz.
3.5 Hz/Sec.
240VDC (230VAC Input)
400VDC (380 – 415 AC Input)
500VDC (460VAC Input)
1 to 300 HP, 240VDC
1.5 to 500 HP, 400VDC
2 to 600 HP, 500VDC
3.6 to 980A
120 – 150VDC, 230VAC
200 – 250VDC, 380VAC
220 – 270VDC, 415VAC
240 – 300VDC, 460VAC
Field Voltage Source is selectable between
internal or external supply.
1 – 30HP, 230V; 2 – 60HP, 460V Drive:
150mA – 10 Amperes Continuous
40 – 100HP, 230V; 75 – 200HP, 460V
Drive: 650mA – 20 Amperes (continuous)
125 – 300HP, 230V; 250 – 600HP, 460V
Drive: 650mA – 40 Amperes (continuous)
A 6:1 speed range with an encoder or DC
tach feedback
Programmable enable, time delay, power on
standby
Phase sequence insensitive, Regenerative/
Non–regenerative
6 pulse, full wave, NEMA Code C
150% for one minute, 200% for 10 seconds,
260% for 5 seconds
Tapered current limit, di/dt limit, Instanta-
neous overcurrent, Programmable motor
overload
Speed Regulation:
Encoder –
DC Tachometer –
Armature Voltage –
0.01% of set speed (over a 10:1 speed
range); 0.001% of top speed (over a 100:1
speed range).
0.5% of top speed with 5PY tachometer;
0.1% of top speed with BC42 tachometer.
2% of top speed
Electrical:
Type Drive:
Full Wave Regen, 12 SCR w/Full Wave 1
∅ Field Regulator