Example configuration settings, Adapter settings, Drive settings – Rockwell Automation 22-COMM-C ControlNet Adapter User Manual
Page 76: Example configuration settings -8
7-8
Using Multi-Drive Mode
Adapter Settings
• The adapter Operating Mode Jumper (J7 in
) is set to the
“5x” (Multi-Drive) position.
• The 22-COMM-C adapter parameters are set as follows:
Drive Settings
Parameters for the five drives are set as follows:
Example Configuration Settings
Parameter
Value
Description
12 - [DSI I/O Cfg]
4
“Drives 0-4” (5 drives on 1 node)
14 - [Drv 0 Addr]
(1)
(1)
The settings for these parameters must match the parameter A104 - [Comm Node
Addr] settings in the respective drives.
1
Address of Drive 0
15 - [Drv 1 Addr]
(1)
2
Address of Drive 1
16 - [Drv 2 Addr]
(1)
3
Address of Drive 2
17 - [Drv 3 Addr]
(1)
4
Address of Drive 3
18 - [Drv 4 Addr]
(1)
5
Address of Drive 4
Parameter
Value
Drive 0 Drive 1 Drive 2 Drive 3 Drive 4
P36 - [Start Source]
5
5
5
5
5
P38 - [Speed Reference]
5
5
5
5
5
A103 - [Comm Data Rate]
(1)
(1)
The drive must be reset for a change to this parameter to take effect.
4
4
4
4
4
A104 - [Comm Node Addr]
(2)
The settings for these parameters must match the respective parameter settings in the
adapter (Parameter 14 - [Drv 0 Addr] through Parameter 18 - [Drv 4 Addr]).
1
2
3
4
5
A105 - [Comm Loss Action]
0
0
0
0
0
A106 - [Comm Loss Time]
5
5
5
5
5
0
0
0
0
0