To change the fault action, To set the fault configuration parameters – Rockwell Automation 22-COMM-C ControlNet Adapter User Manual
Page 31

Configuring the Adapter
3-5
To change the fault action
Set the values of Parameters 08 - [Comm Flt Action] and 09 - [Idle Flt
Action] to the desired responses:
Figure 3.3 Fault Action Screens on PowerFlex 4-Class HIM (22-HIM-*)
Changes to these parameters take effect immediately. A reset is not
required.
If Multi-Drive mode is used, the same fault action is used by the adapter
for all of the drives (Drive 0 - Drive 4) it controls.
To set the fault configuration parameters
If you set Parameter 08 - [Comm Flt Action] or 09 - [Idle Flt Action]
to “Send Flt Cfg,” the values in the following parameters are sent to the
drive after a communications fault and/or idle fault occurs. You must set
these parameters to values required by your application:
Changes to these parameters take effect immediately. A reset is not
required.
Value Action
Description
0
Fault
The drive is faulted and stopped. (Default)
1
Stop
The drive is stopped, but not faulted.
2
Zero Data
The drive is sent 0 for output data. This does not command
a stop.
3
Hold Last
The drive continues in its present state.
4
Send Flt Cfg The drive is sent the data that you set in the fault
configuration parameters (Parameter 10 - [Flt Cfg Logic]
and Parameter 11 - [Flt Cfg Ref]).
Parameter
Name
Description
10
Flt Cfg Logic
A 16-bit value sent to the drive for Logic Command.
11
Flt Cfg Ref
A 16-bit value (0 – 65535) sent to the drive as a
Reference.
Comm Flt Action
Parameter:
#
008
Fault
0
VALUE
LIMITS
SEL
!
Idle Flt Action
Parameter:
#
009
Fault
0
VALUE
LIMITS
SEL
!