Rockwell Automation 22-COMM-C ControlNet Adapter User Manual
Page 118
![background image](/manuals/577183/118/background.png)
B-4
Adapter Parameters
13
[DSI I/O Act]
Displays the drives that are active in the
Multi-Drive mode.
Default:
xxx0 0000
Bit Values:
0 = Drive Active
1 = Drive Inactive
Type:
Read Only
14
15
16
17
18
[Drv 0 Addr]
[Drv 1 Addr]
[Drv 2 Addr]
[Drv 3 Addr]
[Drv 4 Addr]
Sets the corresponding node addresses of the
daisy-chained drives when the Operating Mode
Jumper (J7) on the adapter is set for Multi-Drive
operation.
Important: The settings for these parameters
must match the Comm Node Addr parameter
settings in the respective drives. Each setting must
also be unique (no duplicate node addresses).
See
Configuring the RS-485 Network on page 7-7
for a list of other parameters that must be set
correctly in each daisy-chained drive.
Default:
100
Default:
101
Default:
102
Default:
103
Default:
104
Minimum:
1
Maximum:
247
Type:
Read/Write
Reset Required:
Yes
19
[Ref Adjust]
Sets the percent scale factor for the Reference
from the network.
Default:
100.00
Minimum:
0.00
Maximum:
200.00
Type:
Read/Write
Reset Required:
No
Parameter
No. Name and Description
Details
Bit
Definition
No
t U
sed
No
t U
sed
No
t U
sed
Dr
iv
e 4
A
ctiv
e
Dr
iv
e 3
A
ctiv
e
Dr
iv
e 2
A
ctiv
e
Dr
iv
e 1
A
ctiv
e
Dr
iv
e 0
A
ctiv
e
Default
x
x
x
0
0
0
0
0
Bit
7
6
5
4
3
2
1
0
!
ATTENTION: To guard against equipment damage and/or personal injury, note
that changes to Parameter 19 - [Ref Adjust] take effect immediately. A drive
receiving its Reference from the adapter will receive the newly scaled Reference,
resulting in a change of speed.