Instance attributes, Dsi parameter object – Rockwell Automation 22-COMM-C ControlNet Adapter User Manual
Page 142
![background image](/manuals/577183/142/background.png)
C-24
ControlNet Objects
Instance Attributes
DSI Parameter Object
(Continued)
Attribute
ID
Access
Rule
Name
Data Type
Description
7
Get
Online Read Full
STRUCT of:
BOOL[32]
CONTAINER
(1)
CONTAINER
CONTAINER
CONTAINER
WORD
WORD
STRING[4]
UINT
UINT
UINT
INT
BYTE[3]
BYTE
STRING[16]
Descriptor (Refer to pages
Parameter value
Minimum value
Maximum value
Default value
Next parameter
Previous parameter
Units (e.g., Amp, Hz)
Multiplier
(2)
Divisor
Base
Offset
Link (source of the value) (0 = no link)
Always zero (0)
Parameter name
8
Get
Descriptor
BOOL[32]
Descriptor (Refer to pages
9
Get/Set Parameter Value
Various
Parameter value in NVS.
(3)
10
Get/Set RAM Parameter
Value
Various
Parameter value in temporary memory.
11
Get/Set Link
BYTE[3]
Link (parameter or function block that is
the source of the value) (0 = no link)
12
Get
Help Object
Instance
WORD
ID for help text for this parameter
13
Get
Read Basic
STRUCT of:
BOOL[32]
CONTAINER
CONTAINER
CONTAINER
CONTAINER
STRING[16]
STRING[4]
Descriptor (Refer to pages
Parameter value
Minimum value
Maximum value
Default value
Parameter name
Units (e.g., Amp, Hz)
14
Get
Parameter Name STRING[16]
Parameter name
15
Get
Parameter Alias
STRING[16]
Customer supplied parameter name.
16
Get
Parameter
Processing Error
BYTE
0 = No error
1 = Value is less than the minimum
2 = Value is greater than the maximum
(1)
A CONTAINER is a 32-bit block of data that contains the data type used by a parameter value. If signed, the value
is sign extended. Padding is used in the CONTAINER to ensure that it is always 32-bits.
(2)
This value is used in the formulas used to convert the parameter value between display units and internal units.
Refer to
Formulas for Converting on page C-26
(3)
Do NOT continually write parameter data to NVS. Refer to the attention on
.