Installing the Adapter
1. Set the adapter Operating Mode Jumper (J7) for Single (1x) or
Multi-Drive (5x) operation (see
below). For complete details on Multi-Drive mode operation, see
.
Figure 2.1 Setting Single/Multi-Drive Operation and Node Address Switches
2. Set the adapter node address by rotating the Node Address Switches
to the desired value for each digit.
Important: Each node on the network must have a unique address.
The node address must be set before power is applied
because the adapter uses the node address it detects
when it first receives power. To change a node address,
you must set the new value. Then remove and reapply
power to the adapter, or reset the adapter.
The node address switch settings can be verified using a PowerFlex
4-Class HIM, DriveExplorer, or DriveExecutive to view Diagnostic
Item number 28 (listed on
).
Jumper Setting
Description
Right (1x)
position or jumper
missing
Sets the adapter for Single mode (default setting) using a single
drive connection.
Important: In this mode, connections to multiple drives must be
removed since all powered and connected hosts will respond to
any message sent by the adapter.
Left (5x) position
Sets the adapter for Multi-Drive mode using up to 5 different
drives. DSI peripherals (22-HIM-*, 22-SCM-*, etc.) do not
operate with the adapter in this mode.
Switch Settings
Description
00-99
Node address used by the adapter if switches are enabled. The
default switch setting is 02.
Important: If the address switches are set to “00,” the adapter
will use the setting of Parameter 02 - [CN Addr Cfg] for the
node address. Refer to
Setting the Node Address on page 3-3
Node Address
Switches
Operating