4-16

Configuring the I/O

number of words that are required for your I/O in the Input Size and
Output Size boxes. The size will depend on the I/O that you enabled
in the adapter. This information can be found in Parameter 12 -
[DSI I/O Cfg]
in the adapter.

Table 4.B

shows common

configuration Input/Output sizes.

Table 4.B PLC-5/40C Input/Output Size Configurations

8. Then click OK. An address row (in blue text) will be added below

the PowerFlex 40 drive row.

9. Select File > Save to save the I/O configuration file to the computer.

If this is the first time that you saved the project, the Save As dialog
box appears. Navigate to a folder, type a file name, and click Save to
save the configuration to a file on your computer. The Save
Configuration dialog box (

Figure 4.23

) appears. Then click OK to

download the I/O configuration to the scanner.

Figure 4.23 Save Configuration Dialog Box

10. A warning will appear about communication and I/O disruption on

the network. Click Yes.

Input
Size

Output
Size

Logic Command/
Status

Reference/
Feedback

Parameter 12 -
[DSI I/O Cfg]

Parameter 01 -
[Mode]

2

2

Drive 0

Single

4

4

Drives 0-1

Multi-Drive

6

6

Drives 0-2

8

8

Drives 0-3

10

10

Drives 0-4

TIP: If necessary, the N9:0, N10:0, and N11:0 address
defaults can be changed to meet processor address
requirements or eliminate address conflicts.

TIP: If both Save Type choices are available, it is
recommended to select the “Optimize and re-write schedule
for all connections” radio button.