Rockwell Automation 22-COMM-C ControlNet Adapter User Manual
Page 50
4-16
Configuring the I/O
number of words that are required for your I/O in the Input Size and
Output Size boxes. The size will depend on the I/O that you enabled
in the adapter. This information can be found in Parameter 12 -
[DSI I/O Cfg] in the adapter.
shows common
configuration Input/Output sizes.
Table 4.B PLC-5/40C Input/Output Size Configurations
8. Then click OK. An address row (in blue text) will be added below
the PowerFlex 40 drive row.
9. Select File > Save to save the I/O configuration file to the computer.
If this is the first time that you saved the project, the Save As dialog
box appears. Navigate to a folder, type a file name, and click Save to
save the configuration to a file on your computer. The Save
Configuration dialog box (
) appears. Then click OK to
download the I/O configuration to the scanner.
Figure 4.23 Save Configuration Dialog Box
10. A warning will appear about communication and I/O disruption on
the network. Click Yes.
Input
Size
Output
Size
Logic Command/
Status
Reference/
Feedback
Parameter 12 -
[DSI I/O Cfg]
Parameter 01 -
[Mode]
2
2
✔
✔
Drive 0
Single
4
4
✔
✔
Drives 0-1
Multi-Drive
6
6
✔
✔
Drives 0-2
8
8
✔
✔
Drives 0-3
10
10
✔
✔
Drives 0-4
TIP: If necessary, the N9:0, N10:0, and N11:0 address
defaults can be changed to meet processor address
requirements or eliminate address conflicts.
TIP: If both Save Type choices are available, it is
recommended to select the “Optimize and re-write schedule
for all connections” radio button.