Plc-5 example, Example network, Adding the drive and adapter i/o to the controller – Rockwell Automation 22-COMM-C ControlNet Adapter User Manual
Page 46: Plc-5 example -12
4-12
Configuring the I/O
Example Network
After the adapter is configured, the connected drive and adapter will be a
single node on the network. This section provides the steps that are
needed to configure a simple network like the network in
. In
our example, we will configure a PLC-5/40C controller to communicate
with a drive using Logic Command/Status and Reference/Feedback over
the network.
Figure 4.16 Example ControlNet Network
Adding the Drive and Adapter I/O to the Controller
To establish an I/O configuration that can be used between the controller
and drive over a ControlNet network, you must first create an I/O image
for the PLC-5/40C controller’s built-in scanner.
1. Launch RSNetWorx for ControlNet. In the RSNetWorx for
ControlNet window, select File > New to display the New File
screen. Then select ControlNet Configuration as the network
configuration type, and click OK.
2. Select Network > Online to display the Browse for Network screen
).
PLC-5 Example
Node 1
PLC-5/40C Controller
ControlNet Network
(optional redundancy)
Node 2
PowerFlex 40 Drive
with 22-COMM-C
ControlNet Adapter
Node 99
Computer with 1784-PCC
Network Interface Card and
RSNetWorx for ControlNet