Logic Command/Status Words
Appendix D provides the definitions of the Logic Command/Logic
Status words that are used for some products that can be connected to the
adapter. If you do not see the Logic Command/Logic Status for the
product that you are using, refer to your product’s documentation.
Logic Command Word
PowerFlex 4/40/400 Drives
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command
Description
x Stop
0 = Not Stop
1 = Stop
x
Start
(1)
0 = Not Start
1 = Start
x
Jog
0 = Not Jog
1 = Jog
x
Clear Faults
0 = Not Clear Faults
1 = Clear Faults
x x
Direction
00 = No Command
01 = Forward Command
10 = Reverse Command
11 = No Command
x
Not used
x
Not used
x x
Accel Rate
00 = No Command
01 = Accel Rate 1 Command
10 = Accel Rate 2 Command
11 = Hold Accel Rate
x
x
Decel Rate
00 = No Command
01 = Decel Rate 1 Command
10 = Decel Rate 2 Command
11 = Hold Decel Rate
x
x
x
Reference
Select
000 = No Command
001 = Freq Source = Select
010 = Freq Source = Int. Freq
011 = Freq Source = Comm
100 = Preset Freq 0
101 = Preset Freq 1
110 = Preset Freq 2
111 = Preset Freq 3
x
Not used
(1)
A “0 = Not Stop condition (logic 0)” must first be present before a “1 = Start condition” will start the drive.