iMs-4812 Mini TeMperaTUre sensor
introduction
The IMS-4812 Mini Temperature Sensor is designed to connect to the IMS-4000 Host or Node and monitor temperatures in
tight locations (for example, inside equipment racks). The electrical connection between the sensor and IMS-4000 is made
via the attached RJ-45 patch cable. The sensor may be secured inside equipment using double-sided tape (included) or with
tie-wraps.
Cabling
The Mini-Temperature Sensor comes with an attached 7' cable with an RJ-45 plug on the end. If the sensor is close to the
IMS-4000 Host or Node, you can plug the sensor directly to an IMS environmental input. If the cable is too short you can
use the included RJ-45 adaptor and a longer patch cable to extend the length. For applications where the sensor may be far
from the IMS unit, you may utilize your existing network wiring infrastructure. For example, the sensor may be installed in
another room or another floor. Connect the sensor to your structured wiring network via an RJ-45 jack. At the other end,
connect a patch cable from your structured wiring patch panel directly to the Host or Node environment input.
Caution: The IMS sensors are not TCP/IP devices and therefore should not be connected directly to any wiring
infrastructure that is connected to network equipment as a hub, router, or switch. Sensors use RJ-45 plugs and
cables similar to those used with Ethernet devices.
Mounting
The temperature sensor may be mounted directly on a surface using double-sided tape (included) or it may be secured to
equipment using tie-wraps. The choice depends on your application.
Configuration
All IMS Solution sensors are auto-configured when you plug them into the Host or Node. When a new sensor is plugged
into the Host or Node, the configuration is set to the factory default via the Sensor Template. If you have modified these
templates, the configuration will be set to the modified configuration. When a sensor is removed, or the connection is dis-
rupted, the configuration data remains intact but the sensor will go into trouble status and generate a trouble alarm. When
the sensor is plugged in again, or the connection is re-established, configuration data remains unchanged and the sensor
returns to normal operating condition.
Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm. Removing or
unplugging a sensor for more than 60 seconds or plugging in a different sensor at any time will cause a trouble
alarm.
sensor Template (factory default)
specifications
Input Name: Temperature
Low Temperature Limit: 50ºF
High Temperature Limit: 85ºF
Recognition Time: 60 Seconds
Reset Time: 0 Seconds
Data Logging: Active
Voice: temperature.wav
Input Class: Temperature
Range: 5° to 140°F
Humidity: 5–90% RH
Sensor type: solid state ic
Accuracy: +/- 3 degrees F
Connector: 7' cable w/RJ-45 plug
Housing: black plastic
Housing dimensions: 2.13'' l x 0.6'' d x 1.38'' h