beautypg.com

Ims-4821 room humidity sensor w/ display – Sensaphone IMS-4000 Users manual User Manual

Page 109

background image

107

Chapter 7: IMS-4000 Sensors

iMs-4821 rooM hUMiDiTy sensor w/ Display

installation instructions

introduction

The IMS-4821 humidity sensor is designed to connect to the IMS-4000 Host or Node and monitor indoor humidity. The

electrical connection between the sensor and IMS-4000 is made via RJ-45 patch cable (not included). The sensor may be

mounted either on a wall or to a single-gang electrical box.

package Contents

(1) IMS-4821 Humidity sensor
(2) Plastic drywall anchors
(2) #6 Metal tapping screws
(1) 1/16" hex key

Cabling

The humidity sensor connects to the IMS-4000 Host or Node via an RJ-45 cable (e.g. CAT5 cable). The connection from the

sensor to the Host or Node can utilize your existing network wiring infrastructure. For example, the sensor may be installed

in another room or another floor. Connect the sensor to your structured wiring network via an RJ-45 jack. At the other end,

connect a patch cable from your structured wiring patch panel directly to the Host or Node environment input.

Caution: The IMS sensors are not TCP/IP devices and therefore should not be connected directly to any wiring

infrastructure that is connected to network equipment such as a hub, router, or switch. Sensors use RJ-45 plugs

and cables similar to those used with Ethernet devices.

Mounting

The humidity sensor can be mounted directly on a surface or attached to a single-gang electrical box. Consideration should

be given to cable routing before attaching the sensor to the wall. Will the cable go through the wall (cable hidden) or will

it run down the wall (cable visible)? Once this has been determined, run the cable to the location where the sensor will be

installed.

electrical box installation

Bring the RJ-45 cable through the electrical box. Remove the sensor cover by turning the two hex screws on the bottom of

the sensor housing clockwise. Bring the cable through the back of the sensor and connect the cable to the jack as shown in

Figure 1. Attach the sensor to the electrical box using the appropriate screws. Secure the sensor cover by turning the two hex

screws on the bottom of the cover counterclockwise.

Figure 1: 4821 with Cable exiting through back of enclosure