Chapter 7: IMS-4000 Sensors
Configuration
All IMS Solution sensors are auto-configured when you plug them into the Host or Node. When a new sensor is plugged
into the Host or Node, the configuration is set to the factory default via the Sensor Template. If you have modified these
templates, the configuration will be set to the modified configuration. When a sensor is removed, or the connection is dis-
rupted, the configuration data remains intact but the sensor will go into trouble status and generate a trouble alarm. When
the sensor is plugged in again, or the connection is re-established, configuration data remains unchanged and the sensor
returns to normal operating condition.
Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm. Removing or
unplugging a sensor for more than 60 seconds or plugging in a different sensor at any time will cause a trouble
alarm.
sensor Template (factory default)
specifications
Input Name: Contact Bridge
Bridge:
Recognition Time: 3 Seconds
Input: Normally Open or Normally Closed dry
contact
Reset Time: 0 Seconds
Source/Sense Voltage: 14VDC
Data Logging: Active
Source/Sense Current: 10mA
Voice: dry contact.wav
Cable/Connector: 7' cable with RJ-45 plug
Input Class: Other
Operating
Temperature Range: 32° to 122°F (0° to 50°C)
Housing: Black plastic
Dimensions: 2.13" x 0.6" x 1.38"
Door Switch
Normality: Normally Closed
Dimensions: 2.0" x 0.4" x 0.4" (with screw terminals)
Dimensions: 2.0" x 0.4" x 0.4" (part with magnet)