Sensaphone IMS-4000 Users manual User Manual
Page 116
IMS-4000 Manual
114
Mounting
The sensor can be mounted to a wall or lie flat on the floor. To mount the sensor to a wall, install four drywall anchors (if
necessary) and attach the Current Sensor using four #6 tapping screws.
6.732
2.166
Figure 2: Mounting the sensor
Configuration
All IMS Solution sensors are auto-configured when you plug them into the Host or Node. The 15A Current Sensor will
identify itself as a 4-20mA transducer. On the Properties screen for this sensor you must select the sensor type: Current
Sensor. When a sensor is removed, or the connection is disrupted, the configuration data remains intact but the sensor will
go into trouble status and generate a trouble alarm. When the sensor is plugged in again, or the connection is re-established,
configuration data remains unchanged and the sensor returns to normal operating condition.
Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm. Removing or
unplugging a sensor for more than 60 seconds or plugging in a different sensor at any time will cause a trouble
alarm.
sensor Template (factory default)
specifications
Input Name: Transducer
High Limit: 100
Low Limit: 0
Recognition Time: 60 Seconds
Reset Time: 0 Seconds
Data Logging: Active
Voice: none
Input Class: Other
Range: 0–15 Amps (0-250 VAC, 50/60 Hz)
Operating Temperature: 5° to 104°F (-15 to 40°C)
Operating Humidity: 0-95% RH, non–condensing
Accuracy: ± 2% (from 1-100% of full–scale output
Power Connection: IEC320-C14 inlet / IEC320-C13 outlet
IMS Connection: RJ-45
Housing: Black plastic with mounting ears