Chapter 5: PowerGate

parTs reqUireD

Phillips Screwdriver

9 pin F/F null modem cable

operaTinG enVironMenT

Before you install the IMS-4301 PowerGate be sure that your operating environment meets the physical requirements of the

equipment.

Operating Temperature: 32º–95º Fahrenheit (0º–35º C)

Humidity: 5–90 %RH, non-condensing

Power: 120VAC 60 Hz outlet within 6'

Rack Requirements: Standard 19" equipment rack with supplied mounting bracket hardware. Requires 1.0 EIA

rack mount space.

Tabletop requirements: Flat area which can support an enclosure 17" wide by 10" deep by 2" high.

raCk MoUnT insTallaTion

The IMS-4301 PowerGate can be rack mounted using the included rack mount brackets. Follow the steps below:

1) Attach the rack-mount brackets to the PowerGate with a Phillips screwdriver.
2) Attach the unit to the equipment rack using two pan-head screws per side. Tighten the screws with a Phillips screw-

driver.

3) Plug the power cord into a 120VAC outlet.

Figure 3: Rack-mounted PowerGate Unit

TableTop insTallaTion

The IMS-4301 PowerGate can be installed on a tabletop or shelf. Follow the steps below:

1) Attach the four self-adhesive rubber feet to the four corners on the bottom of the PowerGate.
2) Place the unit on a tabletop or shelf and connect the power cord into a 120VAC outlet.

Figure 4: Tabletop-mounted PowerGate Unit