beautypg.com

Sensaphone IMS-4000 Users manual User Manual

Page 122

background image

IMS-4000 Manual

120

Mounting

The 4-20mA Bridge can be mounted to a wall or lie flat on the floor. To mount it to a wall, install the two drywall anchors

(if necessary) and attach the bridge using the two #6 tapping screws. When installing the sensor on the floor, attach the four

rubber feet to the bottom of the enclosure.

4-20mA

BRIDGE

Current

Flow

IMS

INPUT

+ –

SENSAPHONE

®

REMOTE MONITORING SYSTEM

IMS-4851

Figure 3: Mounting the sensor

Configuration

The 4-20mA Bridge can display a scaled value to match the calibrated range of your transducer. You must have updated ver-

sions of ConsoleView software (v3.0.15) and IMS4k firmware (v3.00) to get this feature. In the ConsoleView Software open

the Channel Properties screen and click the SubType drop down menu, then choose Custom Table Limits. Insert the Low

(4mA) and High (20mA) values for your transducer into the Table Low and Table High fields. The IMS-4000 will display the

scaled value. You may wish to include the units of measure in the Channel Name field.
All IMS Solution sensors are auto-configured when you plug them into the Host or Node. When a new sensor is plugged

into the Host or Node, the configuration is set to the factory default via the Sensor Template. If you have modified these

templates, the configuration will be set to the modified configuration. When a sensor is removed, or the connection is dis-

rupted, the configuration data remains intact but the sen¬sor will go into trouble status and generate a trouble alarm. When

the sensor is plugged in again, or the connection is re-established, configuration data remains unchanged and the sensor

returns to normal operating condition.

Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm. Removing or

unplugging a sensor for more than 60 seconds or plugging in a different sensor at any time will cause a trouble

alarm.

host and node firmware requirements

The 4-20mA Bridge requires the following firmware versions in the Host and Node(s) for sensor compatibility:

iMs-4000 host

• Input board firmware chip version xx.xx.xx.103 or higher

NOTE: Input board firmware is NOT flash upgradeable. A new firmware chip must be installed. For information on

obtaining a new firmware chip, please contact Sensaphone Technical Support at 610.558.2700 or via e-mail at support@

sensaphone.com.

• ConsoleView version 2.04 or higher
• IMS4K OS version 2.41 or higher
• Voice version 2.09 or higher
*Host version information is viewable through the ConsoleView software on the Version Info screen and the Help>About

selection from the main menu.