Sensaphone IMS-4000 Users manual User Manual
Page 110
IMS-4000 Manual
108
hidden cable surface installation
Bring the RJ-45 cable through the wall at the mounting location. Remove the sensor cover by turning the two hex screws
on the bottom of the sensor housing clockwise. Bring the cable through the back of the sensor and hold the sensor housing
against the wall. Use a pencil to mark the hole locations at the top and bottom of the housing. Remove the sensor from the
wall. Install the drywall anchors (if necessary) to the wall. Bring the cable through the back of the sensor and connect it to
the jack as shown in Figure 1. Attach the sensor to the wall using #6 tapping screws. Secure the sensor cover by turning the
two hex screws on the bottom of the cover counterclockwise.
Visible cable surface installation
Remove the sensor cover by turning the two hex screws on the bottom of the sensor housing clockwise. Hold the sensor
housing against the wall. Use a pencil to mark the hole locations at the top and bottom of the housing. Install the drywall
anchors (if necessary) to the wall. Attach the sensor to the wall using #6 tapping screws. Connect the cable to the jack as
shown in Figure 2. Secure the sensor cover by turning the two hex screws on the bottom of the cover counterclockwise.
Figure 2: 4821 with Cable exiting out enclosure bottom
Configuration
All IMS Solution sensors are auto-configured when you plug them into the Host or Node. When a new sensor is plugged
into the Host or Node, the configuration is set to the factory default via the Sensor Template. If you have modified these
templates, the configuration will be set to the modified configuration. When a sensor is removed, or the connection is dis-
rupted, the configuration data remains intact but the sensor will go into trouble status and generate a trouble alarm. When
the sensor is plugged in again, or the connection is re-established, configuration data remains unchanged and the sensor
returns to normal operating condition.
Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm. Removing or
unplugging a sensor for more than 60 seconds or plugging in a different sensor at any time will cause a trouble
alarm.
sensor Template (factory default)
specifications
Input Name: Humidity
Low Limit: 20%
High Limit: 60%
Recognition Time: 60 Seconds
Reset Time: 0 Seconds
Data Logging: Active
Voice: humidity.wav
Input Class: Humidity
Range: 5–95%
Temperature: 32° to 158ºF (0° to 70ºC)
Accuracy: +/- 3%
Connector: RJ-45
Housing: white plastic