121
Chapter 7: IMS-4000 Sensors
iMs-4000 node
• Firmware version 2.19 or higher.
*Node version information is viewable through the ConsoleView software on the Node Properties>Diagnostics screen.
sensor Template (factory default)
specifications
Input Name: Transducer
Recognition Time: 3 Seconds
Reset Time: 0 Seconds
Data Logging: Active
Voice: None
Input Class: Other
Input: 4–20mA DC
Current Limit: 50mA
Input Impedance: Variable (1000W @ 4mA, 260W @ 20mA)
Accuracy: ± 0.25%
IMS Connection: RJ-45
Operating Temperature
Range: 32° to 122°F (0° to 50°C)
Housing: Black plastic with mounting ears