Sensaphone IMS-4000 Users manual User Manual

Page 112

background image

IMS-4000 Manual

110

Mounting

The sensor can be mounted to a wall or lie flat on the floor. To maximize the coverage of the WaterRope, install the sensor

close to the area to be monitored. For wall mounting, install the Water Detection Sensor close to the floor. Install the two

drywall anchors (if necessary) and attach the Water Detection Sensor using the two #6 tapping screws. When installing the

sensor on the floor, attach the four rubber feet to the bottom of the enclosure.

Figure 2: Mounting the sensor

Configuration

All IMS Solution sensors are auto-configured when you plug them into the Host or Node. When a new sensor is plugged

into the Host or Node, the configuration is set to the factory default via the Sensor Template. If you have modified these

templates, the configuration will be set to the modified configuration. When a sensor is removed, or the connection is dis-

rupted, the configuration data remains intact but the sensor will go into trouble status and generate a trouble alarm. When

the sensor is plugged in again, or the connection is re-established, configuration data remains unchanged and the sensor

returns to normal operating condition.

Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm. Removing or

unplugging a sensor for more than 60 seconds or plugging in a different sensor at any time will cause a trouble

alarm.

sensor Template (factory default)

specifications

Input Name: Water Sensor

Recognition Time: 3 Seconds

Reset Time: 0 Seconds

Data Logging: Active

Voice: water sensor.wav

Input Class: Water

Sensing Method: Conductivity

Sensor: Polymer core cable with 2 sensing wires

IMS Connection: RJ-45

Housing: black plastic with mounting ears