beautypg.com

Sensaphone IMS-4000 Users manual User Manual

Page 94

background image

IMS-4000 Manual

92

hidden cable surface installation

Bring the RJ-45 cable through the wall at the mounting location. Remove the sensor cover by turning the two hex screws

on the bottom of the sensor housing clockwise. Bring the cable through the back of the sensor and hold the sensor housing

against the wall. Use a pencil to mark the hole locations at the top and bottom of the housing. Remove the sensor from the

wall. Install the drywall anchors (if necessary) to the wall. Bring the cable through the back of the sensor and connect it to

the jack as shown in Figure 1. Attach the sensor to the wall using #6 tapping screws. Secure the sensor cover by turning the

two hex screws on the bottom of the cover counterclockwise.

Visible cable surface installation

Remove the sensor cover by turning the two hex screws on the bottom of the sensor housing clockwise. Hold the sensor

housing against the wall. Use a pencil to mark the hole locations at the top and bottom of the housing. Install the drywall

anchors (if necessary) to the wall. Attach the sensor to the wall using #6 tapping screws. Connect the cable to the jack as

shown in Figure 2. Secure the sensor cover by turning the two hex screws on the bottom of the cover counterclockwise.

J2

Deg C

Deg F

Figure 2: 4810 with Cable exiting out enclosure bottom

Configuration

All IMS Solution sensors are auto-configured when you plug them into the Host or Node. When a new sensor is plugged

into the Host or Node, the configuration is set to the factory default via the Sensor Template. If you have modified these

templates, the configuration will be set to the modified configuration. When a sensor is removed, or the connection is dis-

rupted, the configuration data remains intact but the sensor will go into trouble status and generate a trouble alarm. When

the sensor is plugged in again, or the connection is re-established, configuration data remains unchanged and the sensor

returns to normal operating condition.

Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm. Removing or

unplugging a sensor for more than 60 seconds or plugging in a different sensor at any time will cause a trouble

alarm.

fahrenheit/Celsius selection

The IMS-4810 can provide temperature readings in either degrees Fahrenheit or Celsius. To select one or the other, remove

the sensor cover by turning the two hex screws on the bottom of the sensor housing clockwise. Locate the black jumper (see

Figure 3) marked J2. Install the jumper in the “Deg F” position for Fahrenheit or the “Deg C” position for Celsius. Secure

the sensor cover by turning the two hex screws on the bottom of the cover counterclockwise.

J2

Deg C

Deg F