88
plUGGinG in eqUipMenT
Attach the power cord from each device to be switched into one of the outlets on the back of the PowerGate2. Be sure to
support heavy cables with tie wraps or some other method to prevent the unit from bending down (See the figure below).
Too much weight in the rear may cause permanent damage to the enclosure.
Figure 7: Cable Support
Each outlet will pass the connected power through from the corresponding power input. Note that the PowerGate2 is
designed for 120VAC circuits only. Each outlet is limited to 15 Amps max via breakers mounted on the front panel.
latched power to outlets
The PowerGate2 design features latching power circuits. Each outlet remains latched ON as long as power is applied to the
corresponding input. This holds true even if main power to the unit is removed. This allows you to pass power from a UPS
through the PowerGate2 to your equipment, without worrying about the PowerGate2 losing power.
powerGaTe2 seTUp Via The iMs ConsoleView sofTware
The PowerGate2 will automatically be recognized by the IMS Host or Node. Within the IMS tree structure an entry called
PowerGate2 will appear within the submenu of the Host and/or Node. To expand the Host or Node submenus you must click
the box with the plus sign next to the appropriate Host or Node. The figure below shows the menu location of a PowerGate2
connected to a Host.
Figure 8: PowerGate2 in Hierarchy
To assign labels to the PowerGate2, right-click on PowerGate2. The following screen will appear:
Figure 9: PowerGate2 Setup