‎Chapter 6 Device C O N T R O L A N D U P G R A D I N G

EM13x Series SMART MULTIFUNCTION METER

99

Chapter 6 Device Control and

Upgrading

This section describes operations on the meter you can perform from
the front display or via PAS. To access device control options from PAS,
you should have your meter online.

6.1 Resetting Accumulators, Maximum Values and Files

Using the Front Display

Select the RESET entry from the main menu. See

Viewing and

Changing Setup Options

in Chapter 3 for information on configuring

parameters via the front display.

To reset the desired values:

Highlight the middle window by pressing briefly the SELECT button.
Select a reset entry by scrolling through the list with the UP and

DOWN arrow buttons.
Press the SELECT button briefly to highlight the lower item.
Press and hold the ENTER button for 5 seconds.
Release the button.
The do entry is replaced with done showing the operation is complete.

Table 20 shows the reset options available from the front display.

Table 20: Front Display Reset Options

Display Label

Description

Power Dmd

Clears power maximum demands

V/A Dmd

Clears ampere and volt maximum demands

Min/Max

Clears Min/Max log

Counters

Clears all counters

Counter 1 – Counter 4

Clears counter #1-#4

Diagnostics

Clears device diagnostics

Using PAS

Ensure that the On-line button on the PAS toolbar is checked, and
then select Reset from the Monitor menu.