‎Chapter 5 Configuring T H E E M 1 3 X S E R I E S

EM13x Series SMART MULTIFUNCTION METER

63

Setting up the Ethernet

Using the Front Display

Select Net from the main menu. See

Viewing and Changing Setup

Options

in Chapter 3 for information on navigating in menus.

See the table below for available network options.

Using PAS

Select Communications Setup from the Meter Setup menu, and then
click on the Network Setup tab.

Figure ‎5-2: Communication Setup Dialog Box – Network Setup Tab

The following table lists available network options.

Table 4: Ethernet Setup Options

Display Label

Parameter

Default

IP Address

Device IP Address

192.168.0.203

Subnet Mask

Network Subnet Mask

255.255.255.0

Def. Gateway

Network Default Gateway

192.168.0.1

TCP Service Port

502 = Modbus/TCP

20000 = DNP3/TCP

502

NOTES

The meter provides the permanent MODBUS TCP server
on port 502.

Selecting the DNP3 TCP service port launches the
second DNP3 TCP server allowing simultaneous
connections on both TCP ports. Selecting the Modbus
TCP port disables the DNP3 TCP server.

The TCP service port can also be changed trough the COM2 serial
port setup. Changing the communication protocol for the port
automatically changes the TCP port for the Ethernet.

Net IP Address
192.168.000.203