Appendix a, Technical specifications, Appendix a technical specifications – SATEC EM132-133 Manual User Manual
Page 126: A.1 environmental conditions, A.2 construction, A.3 three phase power supply – em133-se, A.4 auxiliary power supply
Appendix A Technical Specifications
126
EM13x Series SMART MULTIFUNCTION METER
Appendix A Technical Specifications
A.1
Environmental Conditions
Operational ambient temperature limit range: –25
C to +60
C
Specified ambient temperature range: –20
C to +60
C
Long-term damp heat withstand according to IEC 68-2-3 <95% (non
condensing), +40
C
Transport and storage temperature range: –30
C to +85
C
IEC 60068-2-6, AS 60068-2-6 [18]: Vibration
Frequency range: 10Hz to 150Hz
Vibration time (each axis): 75 min
Sweep rate: 1 oct/min
Max Vibration level: 10 m/s
2
(1g), f > 60Hz
IEC 60068-2-27, AS 60068-2-27 [19]: Shock
Shock level: 30 g
Time duration: 18 ms
Shape: Half sine
Number of shocks: 18
A.2
Construction
Case enclosure: Reinforced Polycarbonate
Packaging case: Carton and Stratocell® (Polyethylene Foam) brackets
Labels: Polyester film (UL94-V0)
A.3
Three Phase Power Supply – EM133-SE
Indirect Connection
Rated input from 1, 2 or 3 phases: 3 x 120-277 VAC 50/60Hz Burden 2VA
per phase
Direct Connection
Rated input from 1, 2 or 3 phases: 3 x 120-230 VAC 50/60Hz Burden 2VA
per phase
Isolation:
Input to ground: 4000V AC
Wire size: up to 12 AWG (up to 3.5 mm2)
A.4
Auxiliary Power Supply
Rated input: 40-300VAC 50/60Hz, 40-300VDC, Burden 5VA
Frequency range operation 25-400 Hz
Isolation:
Input to ground: 4000V AC
Wire size: up to 12 AWG (up to 3.5 mm2)