beautypg.com

A.12 measurement specifications – SATEC EM132-133 Manual User Manual

Page 132

background image

‎Appendix A Technical Specifications

132

EM13x Series SMART MULTIFUNCTION METER

A.12 Measurement Specifications

Table 22: Measurement Specifications Parameters

Parameter

Full Scale @ Input

Range

Accuracy

Range

%

Reading

% FS

Conditions

Voltage, V

120VxPT @ 120V

400VxPT @ 690V

0.2

0.2

0.02

0.02

10% to 120%

10% to 115%

0 to 1,150,000 V

Starting voltage

1.5-5.0% FS (selectable)

Line current, A

CT

0.2

0.02

For In = 5A

1% to 200% FS

For In = 1A

2% to 200% FS

Starting current 0.1% FS

Line current

50 A

0.2

0.02

2% to 200% FS

Starting current 0.1% FS

Active power, kW 0.36

PT

CT @ 120V

1.2

PT

CT @ 690V

34.5 @(230V,50A)

0.3

0.02

|PF|

0.5

1

-10,000,000 kW to

+10,000,000 kW

Reactive power,

kvar

0.36

PT

CT@ 120V

1.2

PT

CT @ 690V

34.5 @(230V,50A)

0.3

0.03

|PF|

0.9

1

-10,000,000 kvar to

+10,000,000 kvar

Apparent power,

kVA

0.36

PT

CT @ 120V

1.2

PT

CT @ 690V

34.5 @(230V,50A)

0.3

0.02

|PF|

0.5

1

0 to 10,000,000 kVA

Power factor

1.000

0.2

|PF|

0.5,

I

2% FSI

-0.999 to +1.000

Frequency

50 Hz

60 Hz

25 Hz

400 Hz

0.02

0.02

0.04

0.04

V

L-N

> 25V

15 Hz to 70 Hz

15 Hz to 70 Hz

15 Hz to 70 Hz

320 Hz to 480 Hz

Total Harmonic

Distortion, THD

V (I), %Vf (%If)

999.9

1.5

0.2

THD

1%,

V

10% FSV and

V

L-N

> 25V,

I

10% FSI

0 to 999.9

Total Demand

Distortion, TDD,

%

100

1.5

TDD

1%,

I

10% FSI,

V

L-N

> 25V

0 to 100

Active energy

Import & Export

In = 5 and 1 A

Class 0.5S under conditions as per

IEC 62053-22:2003 at 50/60 Hz

0 to 999,999,999 kWh

Reactive energy

Import & Export

In = 5 and 1 A

Class 0.5S under conditions as per

IEC 62053-22:2003, |PF|

0.9 and

at 50/60 Hz

0 to 999,999,999 kvarh

Apparent energy In = 5 and 1 A

Class 0.5S under conditions as per

IEC 62053-22:2003 at 50/60 Hz

0 to 999,999,999 kVAh

PT - external potential transformer ratio

CT - primary current rating of the external current transformer

FSV - voltage full scale

FSI - current full scale

Vf - fundamental voltage
If - fundamental current
NOTES:

Accuracy is expressed as

(percentage of reading +

percentage of full scale)

1 digit. This does not include

1

@ 80% to 120% of voltage FS, 1% to 200% of current FS at (In = 5 and 1 A), 2% to 200% of

current FS 50 A and frequency 50/60 Hz