beautypg.com

A.5 input ratings – SATEC EM132-133 Manual User Manual

Page 127

background image

‎Appendix A Technical Specifications

EM13x Series SMART MULTIFUNCTION METER

127

A.5

Input Ratings

Voltage Inputs

Model with 3 Phase Power Supply (EM133-SE)

Operating range: up to 277/480VAC

Frequency range measurement 50-60 Hz

Burden for 277V: < 1.5 VA

Burden for 120V: < 2 VA

Model with Aux. Power Supply:

Operating range: up to 400/690 VAC

Measurement range: direct input and input via PT up to 828VAC line-to-
line, up to 480VAC line-to-neutral

Frequency range measurement 25-400 Hz

Burden for 400V: < 0.4 VA

Burden for 120V: < 0.04 VA

Over-voltage withstands: 1000 VAC continuous, 2000 VAC for 1 second

Wire size: up to 12 AWG (> 3.5mm2)

Input impedance: 1000 k

Current Inputs (via CT)

Wire size: 8 AWG (> 16 mm2)

Galvanic isolation: 4000V AC

5A secondary (standard)

Operating range: continuous 10A RMS

Frequency range measurement 25-400 Hz

Burden: < 0.2 VA @ In=5A

Overload withstanding:

15A RMS continuous, 300A RMS for 1 second

1A secondary (option)

Operating range: continuous 2A RMS

Frequency range measurement 25-400 Hz

Burden: < 0.02 VA @ In=1A

Overload withstanding:

3A RMS continuous, 80A RMS for 1 second

100A direct (option)

Operating range: continuous 100A RMS

Frequency range measurement 40-400 Hz up to 100A

Frequency range measurement 25-400 Hz up to 50A

Burden: < 0.02 VA @ In=50A

Overload withstanding:

120A RMS continuous, 2500A RMS for 1 second

40mA secondary – with external CT (option)